Ekofires eko 4015 Troubleshooting Guide Page 10

  • Download
  • Add to my manuals
  • Print
  • Page
    / 16
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 9
8
Release the pressure test point screw, and attach a pressure gauge.
Light the fire on the HIGH setting. To commission the appliance,
the operating pressure must be in accordance with the figures stat-
ed in section 2.0 of these instructions. The fire is factory set to
achieve the correct flow rates at the specified operating pressure.
Any significant variation in the operating pressure could indicate
a supply problem. If the operating pressure is too high, the gas
supply meter/governor may be set incorrectly. This should be
checked with the fire running and if necessary reset by the gas supplier. If the operating pressure is too low, then check
the meter/governor pressure with the appliance running. If this is less than the inlet pressure stated in section 2.0 of
these instructions it will need to be reset by the gas supplier. If the inlet pressure is too low, but the meter/governor
pressure is acceptable, then a problem in the supply pipework is to be suspected. Upon satisfactory checking of the
inlet pressure, turn the fire off, disconnect the pressure gauge and refit the test point screw. Light the fire and check
for gas soundness. In the event that the inlet pressure is not in accordance with the figures stated in the data section
of these instructions, the appliance must not be commissioned, and the problem investigated and rectified.
This fire is fitted with a flue spillage safety device (ODS).
If the fire shuts down during use for no apparent reason then several things may be suspected. If a door or window has
been opened creating a draught, then pilot disturbance is the problem, and removal of the draught should resolve this.
Re-check the gas pressure to ensure it is adequate (see section 2.0). The thermocouple connection into the back of the
gas control valve may also have worked loose during installation, in this case re-tighten.
If pilot disturbance is not the cause, then the ODS safety system may be in operation. Switch the appliance OFF, check
the flue and carry out any remedial work required. Relight the fire and carry out a spillage test. DO NOT allow the appli-
ance to be used if it continues to fail a spillage test.
The aeration hole of the pilot must be carefully cleaned out on each annual service to ensure continued function of the
ODS.The spillage monitoring system shall not be adjusted, modified, or put out of operation by the installer. Any spare
parts fitted MUST be of a type supplied for the purpose by the appliance manufacturer. If the fire is not spilling, then
further guidance should be sought, using the Troubleshooting section as a guide.
Close all doors and windows to the room containing the appliance. Let the fire run on HIGH for five minutes. Take a
smoke match and put in the smoke match tube provided. Light the smoke match and position the end of the smoke
match tube centrally next to the draught diverter as shown in figures 18 and 19.
All the smoke should be drawn away up the flue.
Any smoke returning into the room indicates that spillage is occurring.
If the spillage test fails and the spigot restrictor is fitted, remove the spigot restrictor, re-fit and re-test. If the initial
spillage test fails, run the fire for a further 10 minutes and repeat the test. When the test has been completed satisfac-
torily, repeat with any extractor fans in the premises running on the highest setting, and any communicating doors
open. Finally, repeat with all doors open.
DO NOT allow the fire to be used until the test is satisfactorily passed.
9.6 SETTING PRESSURE
9.7 FLUE SPILLAGE MONITORING SYSTEM
© 2012 Focal Point Fires plc.
9.8 TESTING FOR SPILLAGE
Figure 19
Section view of draft diverter
Figure 18
Note : insert smoke match
tube until end of tube
touches draft diverter baffle
=
=
Note : insert smoke match
tube centrally
Control Type Test point location
Manual Shown in figure 17
Slide Left hand side of burner
Figure 17
GB IE
Page view 9
1 2 ... 5 6 7 8 9 10 11 12 13 14 15 16

Comments to this Manuals

No comments